ACTIVATING
A TEXT PAGE WHEN AN ALARM IS ACTIVATED
- Go
to "PROJECT MENU" and select "RDA SETUP" in
the DESIGNER Software.
- Go
to "PLC "at the "RDA SETUP MENU" and click
on the "ENABLE" box.
- Select
the PLC Address you wish to use, i.e. Internal Relay, Data Registers,
etc. Enter the PLC Address in the box. IMPORTANT: Data
Register "X" that was selected is assigned as the "Page
Request" register. D.R. "X+1" will control LEDs
1 through 16 on the UniOP Panel. D.R. "X+2" will be
assigned to control LEDs 17 through 32. D.R. "X+3" will
control the PLC Control Word on the UniOP Panels.
- Click
on the "CTRL "box.
- Click
"OK"
- Go
to the "PROJECT MENU" and select "ALARMS"
or select the light bulb icon on the toolbar.
- Setup
the alarms by assigning a head address of a bit or internal relay.
This bit is assigned as Alarm #1. The next bit in that group from
the PLC will be Alarm #2. These must be consecutive register addresses
from the PLC.
- Type
in the desired text for Alarm #1.
- Select
"CURRENT ALARM OPTIONS" and enter the Page Number of
the Text Page you wish the panel to go to when this alarm is activated.
- If
this alarm needs to be acknowledged by the operator then select
"ACKNOWLEDGE".
- Click
"OK"
- Go
to "KEYBOARD MACRO EDITOR".
- Select
the "ALARM" Tab.
- Select
an available UniOP Key from the top of the Macro Editor by scrolling
to the right or left and highlighting the desired key. When the
selected key is pressed during this alarm condition the UniOP
Panel will go to the Page select earlier in the setup.
CONFIGURING
A SERIAL PRINTER TO PRINT REPORTS FROM THE EXOR PANEL
- When
using an Exor 24HS Serial Printer a PFI-4-1250 RS-232 Converter
P.C. board is required which plugs into the back of the printer.
- An
Exor Dual Output Power Supply is also required, Exor Part Number
PWR-ALFA.
- An
Exor cable CA119 connects the printer's serial port to the PC/Printer
port on the Exor Operator Interface panel.
- The
Designer Software needs to be configured to match the serial communication
parameters that are setup in the printer. In Designer go to the
top menu and select Project then select Panel Setup and finally
select Printer Setup. Set the communication parameters to 9600
baud, 8 data bits, 1 stop bit and no parity. Select TTY-Printer
at the top, Width of 20, Length of 10, Auto LF should be set to
"CR", Eject set to "LF", and Protocol set
to "None".
- The
printer DIP switches should be set as follows.
1: |
OFF |
9600 BAUD |
2: |
ON |
9600 BAUD |
3: |
ON |
9600 BAUD |
4: |
OFF |
FLAG TYPE TRANSMISSION PROTOCOL |
5: |
OFF |
NOT USED |
6: |
OFF |
8 DATA BITS, 1 STOP BIT, AND NO PARITY |
7: |
OFF |
8 DATA BITS, 1 STOP BIT, AND NO PARITY |
8: |
OFF |
8 DATA BITS, 1 STOP BIT, AND NO PARITY |
DESIGNER
SOFTWARE STARTUP
- Click
"PROJECT MENU"
- Click
"CHANGE CONTROLLER DRIVER" and select the matching PLC/Controller
that the Exor UniOP Panel will be interfacing with and then click
on "OK"
- Click
"PROJECT MENU"
- Click
"CONTROLLER SETUP" and select the proper CPU, communication
settings, etc. for the PLC/Controller being used. If you are not
interfacing to a network of PLCs be sure the 1:N or similar networking
control box is not checked.
- Click
"PANEL SETUP" and click on the up/down arrow to select
the UniOP panel display for your MMI (Man Machine Interface) project
and then click "OK".
- The
panel that you have selected will de displayed on your monitor.
Each page on the Exor panel contains 32 lines. Depending on the
type of display purchased 2, 4, or 16 of these lines will be displayed
on the face of the UniOP panel at one time. You can use the Exor
Cursor Keys in the Macro Editor to scroll through these lines
one line at a time, jump to the next 2, 4, or 16 or simply not
use the lower lines on the display.
DOWNLOAD
THE PROJECT FILE TO THE UNIOP PANEL
- Save
your Project file by clicking on the Diskette icon or using "FILE"
"SAVE" from the top menu.
- Press
and hold the ENTER Button on the front of the Exor UniOP Panel
for approximately two seconds. When using a Touchscreen press
and hold a blank spot on the screen.
- The
UniOP Panel will go to the System Mode and display two lines of
headings. Use the Exor UniOP Panel's right arrow key to move to
the CONFIG Heading and press the ENTER key on the UniOP panel.
The panel will now be in Configuration Mode which will allow the
Project File on the computer to be transferred.
- From
the computer click on the menu "TRANSFERS" or select
the Download Icon on the Toolbar.
- A
window will pop-up on the monitor displaying the progress of the
download. A message will indicate that the transfer is complete.
- Click
"OK" and the UniOP Panel will automatically go into
Operation Mode. The UniOP Panel is now ready to communicate with
the PLC/Controller
EXOR
CABLE CHANGES
- If
the Exor Panel Hardware Version is earlier than 0041 than you
need to purchase a new programming cable, Part Number CA2OLD.
This is a 9 Pin cable with RTS and CTS jumpered together. The
newer Exor panels have a "Pass-Through Mode" feature
that requires a different cable arrangement. The newer CA2 programming
cable does not jumper RTS and CTS.
HOW
DO I ADD AN UP AND DOWN ARROW TO MY EXOR CP/MD PROJECT PAGE?
- Download
the EXORARRW.FON file and copy it to your C:\Windows\System subdirectory.
Click this file name to download it: exorarrw.fon
- Open
your Exor Project File in Designer
- Go
to the top menu and select Options
- Select
Run Font Editor
- Select
File
- Select
Open
- Select
file: exorarrw.fon
- Click
OK
- Select
File
- Select
Install / View Installed Fonts
- Select
CP/MD 4x20 LCD
- Click
on Install Font
- Select
Yes to install exorarrw font file
- Click
OK
- Exit
Font Editor
- Go
to Designer top menu and select Project
- Select
Font
- Press
the Down Arrow to highlight EXORARRW
- Click
OK
- Save
File
- To
copy an Up or Down arrow into your project go to the Designer
top line menu and select Edit
- Select
Special Characters
- Scroll
to the right to view the last 2 characters shown - an Up Arrow
and a Down Arrow
- Click
on each one and drag it to any free space on your project page
- Close
out the Special Characters Box
- Highlight
the Down Arrow character and select the Cut Icon (Scissors) on
the tool bar
- Go
to the upper far right corner of your project page and select
the Paste Icon from the toolbar
- This
should be used when a project page is longer than the 2 or 4 lines
that are visible to prompt the operator to press the Down Arrow
to scroll the page downwards.
- Repeat
the Cut and Paste procedure to move the Up arrow to the last line
that you intend to use in your project page. This prompts the
operator that the last line in this page has been reached and
the Up Arrow can be used to scroll back up.
HOW
DO I COMPLETELY ERASE THE EXOR PANEL'S PROJECT?
- Press
and hold the ENTER key on the front of the Exor panel for several
seconds until the Command menu appears.
- Use
the arrows to move the cursor to the "CFG" (Configuration)
menu heading.
- Press
the ENTER key to go to the Configuration Mode.
- Press
the following arrow keys in the exact order shown: Left, Right,
Up, Left, Right, Down.
- Remove
power from the Exor panel and the internal memory will be totally
erased. This is the normal condition that an Exor panel would
be in when it is just purchased. When it is powered up it will
be in Configuration Mode awaiting a project file to be downloaded
to it. This is not necessary when changing the project file or
the PLC driver.
RED
FLT LED IS CONSTANTLY FLASHING
- Check
that the Lithium battery is properly installed in the Exor Panel
or if it is a few years old then replace the battery. The battery
maintains the Exor internal Real Time Clock and Recipes. It is
not required to store the project file.
|